CLAMP ON EARTH TESTER
FT6380-50
Easy Pole Clamp-On Ground Resistance Tester with
Super Slim Jaw
The FT6380-50 measures grounding resistance simply by clamping to multiple-grounded ground wires. No auxiliary grounding rod is needed, and there is no need to disconnect the ground wire from the grounding rod. The compact, low-profile sensor can be used to clamp ground wires with ease, and also provide AC current measurement functionality and can measure currents ranging from leakage current on the order of several mA to load currents of up to 60 A.
CAT IV 600 V
Key Features:
• Compatible with Hioki common free App GENNECT Cross (Optional Wireless Adapter Z3210 is necessary)
• Wirelessly transfer measurement data to Excel forms for input (Will be supported by the 2021 upgrade)
• Earth resistance measurement for multi-grounded systems
• Measure leak current with absolute certainty with highly sensitive 0.01 mA resolution (at 20.00 mA range)
• Measure load current up to 60.0 A range
• Clamp at the narrowest point
Multiple grounding can be easily checked with the clamps.
| |
Can measure Multi-Grounded systems. Clamp on the earth cable. The instrument has two cores for voltage injection and current measurement. | |
Clamp at the narrowest point! The dramatically slim 0.79 inch (20mm) jaws let you finish your job easily and efficiently. | |
Transfer data via Bluetooth® wireless communication The new FT6380-50 is compatible with the Z3210 wireless adapter (option). | |
Transport to the Excel® file (It will be supported by the 2021 upgrade.) Open an Excel® file and select a cell. | |
Transport to GENNECT Cross GENNECT Cross, a free app designed specifically for use with Hioki measuring instruments, lets you check and manage measurement results and create reports. The software provides a range of functionality that helps manage data in the field, including photographing measurement sites, placing measurement results on photographs, and saving hand written memos. | |
Alarm Function Set the alarm to audibly and visually notify yourself that the resistance or current value exceeds the threshold. | |
High Accuracy and Repeatability Well-designed magnetic shields eliminate the leakage flux between the two cores that often affect measurement accuracy. | |
LCD with beautiful back light With the bright back light, you can easily read the measurement value even in dark locations. | |
Large storage capacity (up to 2,000 data) You can store up to 2,000 measurement values in the field and recall them in your office later. |
Basic specifications (Accuracy guarantee period: 1 year, Accuracy guarantee period after adjustment made by Hioki: 1 year)
Measurement principle | Instrument has two cores for voltage injection and current measurement. From the defined voltage and measured current, the total circuit loop resistance is calculated Note: For multi grounded systems only. In a multi-grounded system, the larger the number of grounding poles, the more accurate the measured value. | ||||
---|---|---|---|---|---|
Earthing resistance range | \0.20 Ω (0.01 Ω resolution) to 1600 Ω (20 Ω resolution), 10 ranges, Zero suppression: Less than 0.02 Ω, Accuracy: ±1.5 % rdg. ±0.02 Ω | ||||
AC Current range | 20.00 mA (0.01 mA resolution) to 60.0 A (0.1 A resolution), 5 ranges, Zero suppression: Less than 0.05 mA, Accuracy: ±2.0 % rdg. ±0.05 mA (30 Hz to 400 Hz, True RMS), Crest factor 5.0 or less (for the 60 A range, 1.7 or less) | ||||
Maximum input current (Current measurement) | 100 A AC continuous, AC 200 A for 2 minutes or shorter (at 50 Hz/60 Hz, requires derating at frequency) | ||||
Maximum rated terminal-to-ground voltage | 600 VAC measurement category IV (anticipated transient overvoltage 8000 V) | ||||
Memory function | 2000 data | ||||
Alarm function | For resistance measurement and current measurement, Beeps when measured value is less than or greater than threshold. | ||||
Other functions | Data hold, Backlight, Filter, Auto power save, Wireless communication (without Z3210 installed)) | ||||
Display | LCD, Max. 2,000 count Display refresh rate: Approx. 2 times/sec. | ||||
Dust-proof and waterproof | IP40 (EN60529) With Jaws Closed | ||||
Power supply | LR6 alkaline battery × 2 | ||||
Continuous operating time | Approx. 40 hours (25 Ω measurement, backlight off, without Z3210 installed) Approx. 35 hours (25 Ω measurement, backlight off, with Z3210 installed and using wireless communications) | ||||
Maximum measurable conductor diameter | φ 32 mm (1.26 in) | ||||
Dimensions and mass | 73 mm (2.87 in) W × 218 mm (8.58 in) H × 43 mm (1.69 in) D, 620 g (21.9 oz) | ||||
Accessories | Carrying case, Resistance check loop (1 Ω±2%, 25Ω±1%), Strap, LR6 alkaline battery × 2, Instruction manual |
FT6380-50E2-12E_new
Catalog: CLAMP ON EARTH TESTER FT6380-50 | Download PDF [2MB] | English |
WIRELESS ADAPTER Z3210 • Increase your work efficiency, by eliminating human errors from manual reporting • Transfer readings on instruments to easy-to-read graphical reports to prove integrity • Compliance with wireless regulations in more than 50 countries and regions |